Alpha Alpha Pro Tec Plus system (50, 70, 90, 115)

System boiler, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoFactory set figures at maximum output from the Section 2.3 table. The MI gives no tolerance. Checked at maximum (100%) in the chimney sweep function (Section 5.7). Wait 1 minute after starting the function before measuring, or at least 3 minutes if the boiler was already running for heating.
50
9.5%
70
9.85%
90
9.45%
115
9.6%
50, 70, 90
10.6%
115
10.7%
CO₂ at low rate
More infoHide infoFactory set figures at minimum output from the Section 2.3 table. The MI gives no tolerance. Checked at minimum (0%) in the chimney sweep function (Section 5.7).
50
9.1%
70
8.85%
90
8.9%
115
9.0%
50
10.1%
70, 90
10.0%
115
10.3%
Maximum CO
More infoHide infoFrom the Section 2.1 technical data table, which doesn’t split by gas type. Section 2.3 also gives nominal CO at 0% O₂: NG 14, 26, 11, 16 ppm and LPG 184, 200, 190, 225 ppm (50, 70, 90, 115). The LPG 115 nominal figure is above the 200 ppm maximum; the MI doesn’t explain this.
200 ppm200 ppm
CO/CO₂ ratio
More infoHide infoMaximum, from Section 2.1. Section 6: if the ratio is above 0.003, clean the heat exchanger and re-test until it is below 0.003.
0.0030.003
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoGas supply pressure from the Section 2.3 table. Section 3.1 says the NG inlet supply pressure must be at least 20 mbar. Check the gas supply working pressure at maximum (100%) in the chimney sweep function (Section 5.7). Measurement point not stated in MI.
20 mbar37 mbar
Gas rate at maximum
More infoHide infoFrom the Section 2.3 table. The LPG figures are printed in l/h there, but the Section 10 performance tables give the LPG burner gas flow rate at maximum output as 50: 3.98, 70: 5.43, 90: 7.17, 115: 8.86 m³/h. The MI doesn’t explain the difference, so both are shown.
50
5.43 m³/h
70
7.4 m³/h
90
9.77 m³/h
115
12.07 m³/h
50
7.7 l/h
70
10.4 l/h
90
13.8 l/h
115
17.0 l/h

From Part No. 1.038054 rev. ST.001455/000 (04/15/D344)

Enter service mode for high and low rate

High rate

  1. Hold A to start the chimney sweep function.
  2. Press the DHW + button (right-hand, tap symbol) for maximum (100%).

Low rate

  1. Press the DHW − button for minimum (0%).
  2. Or: press the CH + and − buttons (left-hand, radiator symbol) to set any output in 1% steps.
Ending the test
  • Hold A again to come out. No time-out given in MI.

Models

ModelGas
Pro Tec Plus 50 NGNG
Pro Tec Plus 70 NGNG
Pro Tec Plus 90 NGNG
Pro Tec Plus 115 NGNG
Pro Tec Plus 50 LPGLPG
Pro Tec Plus 70 LPGLPG
Pro Tec Plus 90 LPGLPG
Pro Tec Plus 115 LPGLPG

Source: Alpha Pro Tec Plus 50, 70, 90 and 115 Installation and Servicing Instructions, Part No. 1.038054 rev. ST.001455/000 (04/15/D344).

Sections: 2.1 Technical data; 2.3 Combustion data; 3.1 Gas supply; 5.7 Chimney sweep function - combustion checking; 6 Routine servicing (combustion check); 10 Performance data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.