Baxi 800 Heat (816, 825, 830)

Heat only (regular), natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoFrom Setting the gas valve (MI 10.3.11), maximum rate in Chimney Sweep mode. The MI says there must always be a difference of 0.4% between the maximum and minimum CO₂ readings.
9.3% ±0.1%
CO₂ at low rate
More infoHide infoFrom Setting the gas valve (MI 10.3.11), minimum rate in Chimney Sweep mode.
8.9% ±0.1%
Maximum CO
More infoHide infoAt both maximum and minimum rate, at the flue gas test point (combustion check flow chart, MI 7.4.2).
< 350 ppm
CO/CO₂ ratio
More infoHide infoAt both maximum and minimum rate (MI 7.4.2). Technical data (MI 3.1) words it as up to a maximum of 0.004; MI 7.4.2, 10.1 and 10.3.11 say less than 0.004.
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoAt the gas meter: 19–23 mbar. Checked with the boiler at maximum rate; the text says at least 17 mbar at the valve and 18 mbar at the gas cock (MI 7.5.1, Fig. 41). Technical data gives a nominal dynamic inlet pressure of 20 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes (MI 3.1).
816
1.75 m³/h
825
2.73 m³/h
830
3.27 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (MI 7.4.2, 10.1).
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7749898-01 (3/20)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi 816 Heat41-470-77NG
Baxi 825 Heat41-470-78NG
Baxi 830 Heat41-470-79NG

Source: Baxi 800 Heat Installation and Service Manual, Gas Fired Wall Mounted Condensing Boiler, 7749898-01 (3/20).

Sections: 3.1 Technical Data; 7.4.1 ’Chimney Sweep’ Mode (CSM); 7.4.2 ’Chimney Sweep’ Mode - Combustion Check; 7.5.1 Check the Operational (Working) Gas Inlet Pressure; 10.1 General; 10.3.11 Setting the Gas Valve (CO2 Check).