Baxi 800 System 2 (18, 24, 30)

System boiler, natural gas and LPG

Not in the database yet:
  • LPG supply pressure in Tab.2 (MI section 3.1.3): the characters are lost in the PDF and can’t be read

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoFront panel closed, boiler in chimney sweep at maximum. NG values are for G20 only: for G20 with up to 20% hydrogen, use the O₂ values to calibrate the gas valve. Same figures for all three sizes. The MI prints them with decimal commas (9,0%).
9.0% (8.8 to 9.4)10.3% (10.2 to 10.7)
CO₂ at low rate
More infoHide infoFront panel closed, boiler in chimney sweep at minimum. NG values are for G20 only: for G20 with up to 20% hydrogen, use the O₂ values to calibrate the gas valve.
8.5% (8.1 to 8.6)9.7% (9.2 to 9.8)
Maximum CO
More infoHide infoThe MI contradicts itself. The service settings table (MI 7.4.3, p. 49) gives CO max <400 ppm, front panel closed. The combustion procedure flowchart (Fig.52, p. 48) says CO must be under 350 ppm at both maximum and minimum rate.
Service settings table
<400 ppm
Combustion procedure
<350 ppm
Service settings table
<400 ppm
Combustion procedure
<350 ppm
CO/CO₂ ratio
More infoHide infoAt maximum and minimum rate (Fig.52). Section 10.1 also says it must be less than 0.004.
<0.004<0.004
O₂ at high rate
More infoHide infoFront panel closed. The MI prints the tolerance ranges high to low. It says that 20% hydrogen in the gas may raise O₂ in the flue gases by about 1.5%, so use the standard O₂ values for the gas used when adjusting.
4.8% (5.2 to 4.1)5.2% (5.4 to 4.6)
O₂ at low rate
More infoHide infoFront panel closed. The MI prints the tolerance ranges high to low.
5.7% (6.5 to 5.6)6.1% (6.9 to 6.0)
Working inlet pressure
More infoHide infoBoiler at maximum rate. NG figures from Fig.44. At the meter: NG 19–23 mbar. Text in MI 7.4.1 says the working pressure at the gas inlet test point (A) must be at least 18 mbar (NG) or 37 mbar (LPG). Permissible pressure drop across system pipework ≤ 1 mbar. Tab.2 gives NG supply pressure 20 mbar; the LPG figure in Tab.2 can’t be read.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Appliance inlet
at least 37 mbar
Gas rate at maximum
More infoHide infoWith any other appliances and pilot lights turned off (MI 7.4.1 Tab.23, same in Tab.8). Gas rate at minimum (Tab.8): NG 0.52 m³/h, LPG 0.38 kg/h, all sizes.
18
1.97 m³/h
24
2.61 m³/h
30
3.26 m³/h
18
1.44 kg/h
24
1.92 kg/h
30
2.4 kg/h
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate (Fig.52, section 10.1).
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7821598 - 03 (4/23)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
800 System 2 18 (818-2)41-470-99Not stated
800 System 2 24 (824-2)41-884-09Not stated
800 System 2 30 (830-2)41-884-08Not stated

Source: Baxi 800 System 2 Installation and Service Manual &amp; Boiler Fiche, 7821598 - 03 (4/23).

Sections: 3.1.2 Certifications; 3.1.3 Gas category; 3.2 Technical data (Tab.8 Combustion characteristics); 7.4.1 Check the operational (working gas inlet pressure and gas rate); 7.4.2 Combustion parameters and chimney sweep function; Fig.52 Combustion procedure; 7.4.3 LPG conversion procedure; 7.4.3 Service settings (p. 49); 7.4.4 Adjusting the gas valve (p. 50); 10.1 Maintenance, general.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.