Baxi Checked against MI

Baxi Duo-tec Combi HE (24 HE, 28 HE, 33 HE, 40 HE)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoIn Calibration Mode at maximum rate (display reads 00), after running the boiler for several minutes, with the analyser probe in the flue adaptor test point. Case on or off not stated in MI.
8.7% ± 0.2
CO₂ at low rate
More infoHide infoIn Calibration Mode at minimum rate (display reads 0). If the CO₂ is reset at either rate, recheck at the other rate.
8.4% ± 0.2
Maximum CO
Not given in MI
CO/CO₂ ratio
Not given in MI
O₂
Not given in MI
Working inlet pressure
More infoHide infoMeasurement point not stated in MI. Technical data gives inlet pressure 20 mbar; commissioning (11.3) says the gas supply pressure should be 20 mb; fault finding (18.1) says the preferred minimum gas pressure is 20 mbar. Fault finding chart I says check the gas supply pressure is greater than 10–11 mbar for natural gas.
20 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes. Commissioning (11.3) gives the same figures as approximate values, measured in Calibration Mode at maximum rate with other gas appliances and pilot lights off.
24 HE
2.61 m³/h
28 HE
3.1 m³/h
33 HE
3.6 m³/h
40 HE
4.36 m³/h

From UK Comp No 5122323 - Iss 3 - 7/07

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Duo-tec Combi 24 HE47-075-23NG
Duo-tec Combi 28 HE47-075-25NG
Duo-tec Combi 33 HE47-075-24NG
Duo-tec Combi 40 HE47-075-26NG

Source: Baxi Duo-tec Combi HE Range installation & servicing instructions, UK Comp No 5122323 - Iss 3 - 7/07.

Sections: Models and GC numbers (page 2); 4.1 Technical Data; 11.3 Checking; 15.1 Checking the CO₂; 18.1 Initial Fault Finding Checks; 18.0 Fault finding chart I.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.