Baxi Duo-tec Combi HE A (24, 28, 33, 40 HE A)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoMeasured at the flue adaptor test point in Calibration Mode, after running the boiler for several minutes (MI 15.1). The same figure is given in MI 13.1.
8.7% ± 0.2
CO₂ at low rate
More infoHide infoChecked after the maximum rate check, with the display reading 0 (MI 15.1). The same figure is given in MI 13.1.
8.4% ± 0.2
Maximum CO
Not given in MI
CO/CO₂ ratio
More infoHide infoGiven in the annual servicing combustion check (MI 13.1).
Less than 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoMeasurement point not stated in MI. Technical data (MI 4.1) gives inlet pressure 20 mbar, commissioning (MI 11.2) says the gas supply pressure should be 20 mbar, and fault finding (MI 18.1) calls 20 mbar the preferred minimum. Fault finding chart I (MI p. 55) says to check the supply pressure is greater than 10–11 mbar.
20 mbar
Gas rate at maximum
More infoHide infoNatural gas G20, after 10 minutes (MI 4.1). MI 11.2 gives the same figures as approximate values, with other appliances and pilot lights off.
24
2.61 m³/h
28
3.1 m³/h
33
3.6 m³/h
40
4.36 m³/h

From UK Comp No 5122323 - Iss 7 - 5/09

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Duo-tec Combi 24 HE A47-075-35NG
Duo-tec Combi 28 HE A47-075-36NG
Duo-tec Combi 33 HE A47-075-37NG
Duo-tec Combi 40 HE A47-075-38NG

Source: Baxi Duo-tec Combi HE A Range installation & servicing instructions, UK Comp No 5122323 - Iss 7 - 5/09.

Sections: 4.1 Technical data; 11.2 Checking; 13.1 Annual servicing; 15.1 Checking the CO2; 18.1 Initial fault finding checks; 18.0 Fault finding chart I.