Baxi EcoBlue Combi (24, 28, 33)

Combi, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoIn chimney sweep mode with the case front panel fitted and the system cold. The valve is checked and set at maximum DHW input (setting 2) and minimum input (setting 1).
8.7% ± 0.2
CO₂ at low rate
More infoHide infoIf CO₂ is reset at one rate, recheck it at the other rate.
8.4% ± 0.2
Maximum CO
More infoHide infoMeasured at the flue gas test point at maximum DHW input and minimum input.
Max rate
< 350 ppm
Min rate
< 350 ppm
CO/CO₂ ratio
Max rate
< 0.004
Min rate
< 0.004
O₂
More infoHide infoThe MI gives O₂ only for the flue integrity check at the air inlet test point (see Flue integrity).
Not given in MI
Working inlet pressure
More infoHide infoFigures from Fig. 41a, with the boiler at maximum rate. At the gas meter: 19–23 mbar. The text in 7.5.1 and the fault finding chart (G) instead say the pressure at the gas cock test point must be at least 17 mbar, and 11.2 gives a preferred minimum of 20 mbar (NG). Technical data gives a dynamic (nominal) inlet pressure of 20 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20), after 10 minutes, with all other appliances and pilot lights off.
24
2.61 m³/h
28
3.05 m³/h
33
3.59 m³/h
Flue integrity
More infoHide infoAt the air inlet test point, with the boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7212134 - 03 (09/14)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Baxi EcoBlue 24 Combi47-075-81NG
Baxi EcoBlue 28 Combi47-075-82NG
Baxi EcoBlue 33 Combi47-075-83NG

Source: Baxi EcoBlue Combi 24 - 28 - 33 Installation and Service Manual, 7212134 - 03 (09/14).

Sections: 3.1 Technical Data; 7.4.1 Checking Combustion - Chimney Sweep Mode; 7.5.1 Check the Operational (Working Gas Inlet Pressure & Gas Rate); 10.1 General; 10.3.25 Setting the Gas Valve (CO2 Check); 11.2 Fault Finding.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.