Baxi EcoBlue Heat (12, 15, 18, 21, 24)

Heat only, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoFrom setting the gas valve (MI 10.3.13), in chimney sweep mode at maximum rate. There must always be a difference of 0.4% between the maximum and minimum CO₂ readings.
9.3% ±0.1%
CO₂ at low rate
More infoHide infoFrom setting the gas valve (MI 10.3.13), in chimney sweep mode at minimum rate.
8.9% ±0.1%
Maximum CO
More infoHide infoChecked at both maximum and minimum rate in the commissioning combustion check (MI 7.4.2).
< 350 ppm
CO/CO₂ ratio
More infoHide infoCommissioning (MI 7.4.2) and servicing (MI 10.1, 10.3.13) say less than 0.004. Technical data (MI 3.1) says up to a maximum of 0.004.
< 0.004
O₂
Not given in MI
Working inlet pressure
More infoHide infoWith the boiler at maximum rate. At the gas meter: 19–23 mbar. MI 7.5.1 says the inlet pressure at the gas valve test point must be at least 17 mbar. Technical data gives a dynamic (nominal) inlet pressure of 20 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
17–21 mbar
Gas rate at maximum
More infoHide infoNatural gas (G20), after 10 minutes, with a CV of 37.78 MJ/m³.
12
1.42 m³/hr
15
1.75 m³/hr
18
2.07 m³/hr
21
2.29 m³/hr
24
2.73 m³/hr
Flue integrity
More infoHide infoAt the air inlet test point, boiler at maximum rate.
O₂ ≥ 20.6%
CO₂ < 0.2%

From 7212435 - 02 (08/14)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
EcoBlue 12 Heat41-470-02NG
EcoBlue 15 Heat41-470-03NG
EcoBlue 18 Heat41-470-04NG
EcoBlue 21 Heat41-470-05NG
EcoBlue 24 Heat41-470-06NG

Source: Baxi EcoBlue Heat 12 - 15 - 18 - 21 - 24 Installation and Service Manual, 7212435 - 02 (08/14).

Sections: 1 Model Range; 3.1 Technical Data; 7.4.1 Chimney Sweep Mode (CSM); 7.4.2 Chimney Sweep Mode - Combustion Check; 7.5.1 Check the Operational (Working) Gas Inlet Pressure; 10.1 General; 10.3.13 Setting the Gas Valve (CO2 Check).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.