Baxi Solo HE heat only (12 HE, 15 HE, 18 HE, 24 HE, 30 HE)
Heat only, natural gas
Combustion figures
| Figure | Natural gas (G20) |
|---|---|
CO₂ at high rate More infoHide infoRate not stated in MI: it gives one CO₂ level for all models, so it is shown at both rates. Check at the flue sampling point. No adjustment of the gas valve is permissible; if the level is higher, the MI says to call Baxi Technical Enquiries. | 9% ± 1% |
CO₂ at low rate More infoHide infoRate not stated in MI: same single CO₂ level as high rate. | 9% ± 1% |
Maximum CO | Not given in MI |
CO/CO₂ ratio More infoHide infoCheck at the flue sampling point. | Up to a maximum of 0.004 |
O₂ | Not given in MI |
Working inlet pressure More infoHide infoCheck at the inlet tapping of the gas valve with the system cold and all controls calling for heat. Do not check at the outlet test point. |
|
Gas rate at maximum More infoHide info2H, G20, 20 mbar, after 10 minutes. The 30 HE is factory set below its maximum and can be altered (MI section 10.8). |
|
From Comp No 5120309 - Iss 3 - 7/07
Enter service mode for high and low rate
High rate
Steps not added yet. Follow the MI.
Low rate
Steps not added yet. Follow the MI.
Ending the test: follow the MI.
Models and GC numbers
| Model | GC number | Gas |
|---|---|---|
| Baxi Solo 12 HE | 41-075-50 | NG |
| Baxi Solo 15 HE | 41-075-46 | NG |
| Baxi Solo 18 HE | 41-075-51 | NG |
| Baxi Solo 24 HE | 41-075-45 | NG |
| Baxi Solo 30 HE | 41-075-44 | NG |
Source: Baxi Solo HE Range installation & servicing instructions, Comp No 5120309 - Iss 3 - 7/07.
Sections: 4.0 Technical Data; 12.1 Commissioning the Boiler; 14.1 Annual Servicing; 15.8 Gas Valve.
Spotted something wrong? Tell us.
Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.