Heating Explained

← All boilers

British Gas Checked against MI

British Gas ICC2 combi (ZWBR 8-30, 11-37)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoAt max. rated heat output (service function 2.0 Operating mode set to Max). No tolerance given in MI. MI 8.1 Tables 15 and 16 and MI 1.9 Table 2 agree. Table 2 lists the propane models as ZWBR 11-30 and ZWBR 14-37; Tables 15 and 16 give the LPG G31 figure under the ZWBR 8-30 and ZWBR 11-37 headings.
8-30
9.4%
11-37
9.2%
11.0%
CO₂ at low rate
More infoHide infoAt min. rated heat output (service function 2.0 Operating mode set to Min). No tolerance given in MI.
9.2%11.0%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
Not given in MINot given in MI
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMI wording: natural gas appliances must not be operated if the gas supply pressure is below 18 mbar or above 24 mbar; LPG appliances must not be operated if it is below or above 37 mbar. Checked at the gas supply pressure test point (Fig. 2, item 7, on the gas valve). MI 5.1 gives the LPG 37 mbar as at the inlet to the appliance. Natural gas appliances are factory set for 20 mbar supply pressure (MI 1.9 Table 2 and MI 8).
Gas valve test point
18–24 mbar
Appliance inlet
37 mbar
Gas valve test point
37 mbar
Gas rate at maximum
More infoHide infoAfter 10 minutes from lighting. NG G20 (CVnet 34.02 MJ/m³); LPG CVnet 88 MJ/m³. MI 1.9 Table 2 gives the LPG figures for the propane models ZWBR 11-30 and ZWBR 14-37. In MI 1.9 Table 2 the LPG figures are under the propane models: 2.2 kg/h under ZWBR 11-30 (the propane version of the 8-30, same heat input) and 2.7 kg/h under ZWBR 14-37 (the propane version of the 11-37).
8-30
3.2 m³/h
11-37
3.9 m³/h
8-30
2.2 kg/h
11-37
2.7 kg/h
Flue integrity
More infoHide infoAt the combustion air testing point (234.1), in chimney sweep mode. MI wording: O₂ must not be less than 20,6%; CO₂ must not exceed 0,2%. For type C13 and C33 flue systems.
O₂ ≥ 20.6%
CO₂ ≤ 0.2%
O₂ ≥ 20.6%
CO₂ ≤ 0.2%

From 6 720 610 602 GB (03.02)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
ZWBR 8-30 ICC241-108-09NG
ZWBR 11-37 ICC241-108-10NG
ZWBR 11-30 propane (8-30 size)Not added yetLPG
ZWBR 14-37 propane (11-37 size)Not added yetLPG

Source: ICC2 combi Installation and Servicing Instructions, 6 720 610 602 GB (03.02).

Sections: 1.6 Layout of appliance; 1.9 Technical data; 5.1 Commissioning; 8 Converting the appliance to different gas types (Checking the gas supply pressure); 8.1 Setting the gas/air ratio; 8.2.1 Testing the O2 or CO2 level in the combustion air; 8.2.2 Testing CO and CO2.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.