Glow-worm Checked against MI

Glow-worm hxi heat only (12hxi, 15hxi, 18hxi, 24hxi, 30hxi, 38hxi)

Heat only, natural gas (30hxi convertible to LPG)

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoCase off (inner casing panel removed), boiler at maximum (MI 11.6). With the inner casing panel fitted the readings increase slightly: NG 9.3% +0.3 −0.5, LPG 10.7% +0.3 −0.8 (MI 10.5, 11.6). The MI contradicts itself for the 38hxi: sections 10.5 and 11.6 give 9.1% +0.2 −0.5 (case on 9.3% +0.3 −0.5) for every size, but Table 2 (MI 1.4) gives the 38hxi 8.8% +0.2 −0.5 case off and 9.0% +0.3 −0.5 case on. Table 2 doesn’t say which rate its figures are for. LPG is for the 30hxi only, after conversion: MI 10.5 gives the propane figure without saying which rate, and MI 11.6 gives no propane figure at maximum. After converting, the LPG conversion section (step 10) says CO₂ should stay between 9.8% and 10.8% with the boiler back in normal running.
12hxi, 15hxi, 18hxi, 24hxi, 30hxi
9.1% +0.2 −0.5
38hxi
9.1% +0.2 −0.5 or 8.8% +0.2 −0.5 (see More info)
10.5% +0.3 −0.7
CO₂ at low rate
More infoHide infoCase off, minimum rate (fan at 1200 ±100 rpm, display flashing 12) (MI 11.6). With the inner case front panel fitted the readings increase slightly: NG 9.3% +0.3 −0.5, LPG 10.7% +0.3 −0.8. For the 38hxi, Table 2 (MI 1.4) gives 8.8% +0.2 −0.5 case off and 9.0% +0.3 −0.5 case on, against 9.1% in sections 10.5 and 11.6 (see CO₂ at high rate). LPG is for the 30hxi only: when converting, the LPG conversion section (step 9) says set CO₂ at minimum to 10.5% ± 0.2%.
12hxi, 15hxi, 18hxi, 24hxi, 30hxi
9.1% +0.2 −0.5
38hxi
9.1% +0.2 −0.5 or 8.8% +0.2 −0.5 (see More info)
10.5% +0.3 −0.7
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
Not given in MINot given in MI
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNo tolerance given. MI 1.3 asks for a steady inlet working pressure of 20 mbar (propane 37 mbar) at the boiler. MI 10.5 says check the supply pressure is 20 mb at the inlet pressure test point on the gas valve with the boiler firing at full rate. LPG (30hxi only): the LPG conversion section says the appliance supply pressure should be 37 mbar; no gas valve test point figure is given for LPG.
Appliance inlet
20 mbar
Gas valve test point
20 mbar
Appliance inlet
37 mbar
Gas rate at maximum
More infoHide infoApproximate, after 10 minutes from cold (Table 2, MI 1.4). The MI contradicts itself for the 24hxi: Table 2 gives 2.58 m³/h, but MI 10.5 gives 2.57 m³/h. MI 10.5 gives 2.0 m³/h for the 18hxi.
12hxi
1.29 m³/h
15hxi
1.61 m³/h
18hxi
2.00 m³/h
24hxi
2.58 m³/h or 2.57 m³/h (see More info)
30hxi
3.02 m³/h
38hxi
4.06 m³/h
Not given in MI

From 0020008153-05 11.05

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
12hxi41-047-73NG
15hxi41-047-74NG
18hxi41-047-63NG
24hxi41-047-69NG
30hxi41-047-64NG
38hxi41-047-71NG

Source: Glow-worm 12hxi, 15hxi, 18hxi, 24hxi, 30hxi, 38hxi High Efficiency Condensing Boilers: Instructions for Use, Installation and Servicing, 0020008153-05 11.05.

Sections: 1.3 Gas Supply; 1.4 Technical Data (Table 2); 10 Commissioning: LPG Conversion - 30hxi only; 10.5 Testing - Gas; 11.6 Combustion Check.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.