Glow-worm Ultrapower sxi system store (100sxi, 170sxi)

System store, natural gas (LPG by conversion)

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoMeasured after 5 minutes (LPG: after 5 minutes at max rate). The servicing table (section 13) calls these nominal and gives NG case off as 9.0 with no tolerance; the specification table (section 1) gives 9.0 ± 0.5. The NG tables don’t name the rate, but the maximum rate check in section 13 refers to them. The MI says NG combustion is factory set and no measurement is necessary at first lighting. Same figures for 100sxi and 170sxi.
Case on
9.2% ± 0.5
Case off
9.0% ± 0.5
Case on
10.2% ± 0.5
Case off
10.0% ± 0.5
CO₂ at low rate
More infoHide infoSection 13 says to go on to check the minimum rate adjustment, but the MI gives no minimum rate figure or procedure.
Not given in MINot given in MI
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
0.0040.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoNominal supply pressure, checked at the gas service isolation valve test point with all other gas appliances working. Measured at the gas valve it can be up to 2 mbar less. The MI says the nominal maximum heat input can be reached at an inlet pressure down to 15 mbar (gas type not stated).
Appliance inlet
20 mbar
Appliance inlet
37 mbar
Gas rate at maximum
More infoHide infoApproximate, after 10 minutes from cold. Minimum: NG 0.48 m³/h, LPG 0.7 kg/h. The central heating range rating table (section 12.7) gives 2.5 m³/h at 24 kW, the highest central heating setting.
3.30 m³/h2.4 kg/h

From 0020048525-04 09.09

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
100sxi41-019-09NG
170sxi41-019-10NG

Source: Glow-worm Ultrapower sxi Installation and Servicing, 0020048525-04 09.09.