Ideal Evomax (30, 40, 60, 80, 100, 120, 150, 30P, 40P, 60P, 80P)

Commercial heat only, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoHot condition (Frame 52 table). The ± 0.5% tolerance is from Table 1; the Frame 52 table gives no tolerance. LPG figures are for the P models.
9.7% ± 0.5%11.4% ± 0.5%
CO₂ at low rate
More infoHide infoHot condition (Frame 52 table). Tolerance from Table 1.
8.7% ± 0.5%10.2% ± 0.5%
Maximum CO
Not given in MINot given in MI
CO/CO₂ ratio
More infoHide infoFrames 55 and 56.
Not greater than 0.004Not greater than 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoMinimum at the boiler inlet with the boiler firing (Frame 31). The inlet pressure test point is on the gas valve on the 30, 40, 60, 80 and 150, and on the inlet gas manifold on the 100 and 120 (Frame 58). Table 2 gives the gas supply as G20 20 mbar and G31 37 mbar. The fault finding charts (MI pp. 52–53) ask whether more than 18 mbar is available at the boiler, which doesn’t match the 17.5 mbar minimum.
Appliance inlet
17.5 mbar minimum
Appliance inlet
37 mbar minimum
Gas rate at maximum
More infoHide infoTable 1. LPG lines are the 30P, 40P, 60P and 80P. Frame 52: after 10 minutes you should read at least 90% of the nominal gas rate.
30
3.2 m³/hr
40
4.3 m³/hr
60
6.4 m³/hr
80
8.7 m³/hr
100
10.8 m³/hr
120
13.0 m³/hr
150
16.2 m³/hr
30
1.26 m³/hr
40
1.69 m³/hr
60
2.53 m³/hr
80
3.41 m³/hr
100, 120, 150
No LPG model in MI

From UIN 206210 A03 (June 2011)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Evomax 3041-750-33NG
Evomax 4041-750-34NG
Evomax 6041-750-35NG
Evomax 8041-750-36NG
Evomax 10041-750-37NG
Evomax 12041-750-38NG
Evomax 15041-750-39NG
Evomax 30P41-750-40LPG
Evomax 40P41-750-41LPG
Evomax 60P41-750-42LPG
Evomax 80P41-750-43LPG

Source: Ideal Evomax 30, 40, 60, 80, 100, 120, 150, 30P, 40P, 60P, 80P installation and servicing, UIN 206210 A03 (June 2011).

Sections: Table 1 Performance data; Table 2 General data; Frame 31 Gas connection; Frame 52 Initial lighting; Frame 55 Safety; Frame 56 Servicing schedule (setting to maximum output); Frame 58 Removal of fan and gas valve assembly.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.