Ideal Checked against MI

Ideal Vogue Max System (15, 18, 26, 32)

System boiler, natural gas

Combustion figures

FigureNatural gas (G20)
CO₂ at high rate
More infoHide infoTable 1 (CO₂ content, Max. CH). The air/gas ratio valve is factory set and must not be adjusted during commissioning.
15
9.4% ± 0.7
18, 26, 32
9.5% ± 0.7
CO₂ at low rate
More infoHide infoTable 1 (CO₂ content, Min. CH).
15
8.3% ± 0.7
18
8.5% ± 0.7
26
8.4% ± 0.7
32
8.2% ± 0.7
Maximum CO
More infoHide infoAt maximum and minimum rate, from the commissioning flowchart (MI p. 73).
Less than 350 ppm
CO/CO₂ ratio
More infoHide infoThe commissioning flowchart (MI p. 73) gives less than 0.0040 at maximum and minimum rate. The servicing schedule (MI 3.1, step 10) prints the limit as 0.004% with a percent sign. Both shown as printed.
Flowchart
less than 0.0040
Servicing schedule
0.004%
O₂
Not given in MI
Working inlet pressure
More infoHide infoChecked at the inlet gas pressure test point on the gas service cock, boiler in service mode maximum rate. At the meter outlet: 19 mb minimum (allowing 1 mb loss across the pipework). The gas cock can lower the reading at its test point (graph in MI 1.8). Table 1 gives the gas supply as 2H – G20 – 20 mbar. MI 1.8 says the boiler can give full output at inlet pressures as low as 14 mb, but other appliances may not.
Appliance inlet
18 mb minimum
Gas rate at maximum
More infoHide infoTable 2 gas consumption, calculated using 38.7 MJ/m³ gross (34.9 MJ/m³ nett). At minimum: 15: 0.310, 18: 0.372, 26: 0.537, 32: 0.661 m³/h. Check at the gas meter at full output with no other appliances in use.
15
1.559 m³/h
18
1.869 m³/h
26
2.695 m³/h
32
3.314 m³/h
Flue integrity
More infoHide infoAt the air inlet test point (where available), boiler at maximum rate. Where no air inlet test point is provided, the MI says a flue integrity check with the analyser is not possible and the flue must be checked visually instead.
O₂ ≥ 20.6% or CO₂ ≤ 0.2%

From UIN 219005 A03 (February 2019)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
Vogue Max System 1541-796-22NG
Vogue Max System 1841-796-23NG
Vogue Max System 2641-796-24NG
Vogue Max System 3241-796-25NG

Source: Ideal Vogue Max System 15 18 26 32 Installation & Servicing, UIN 219005 A03 (February 2019).

Sections: Table 1 General data; Table 2 Performance data; 1.8 Gas supply; 2.23 Commissioning and testing; 2.24 Initial lighting; 2.28 Menu operation (service mode minimum and maximum rate, MI p. 42); 3.1 Servicing schedule; Flowchart for CO level and combustion ratio check (MI p. 72–73).

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.