Vaillant Checked against MI

Vaillant ecoTEC exclusive system (627 VU 256/5-7 H-GB)

System boiler, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoThe manual says to measure the CO/CO₂ content at maximum and minimum load after calibration (sections 7.13.4 and 7.13.5) but gives no CO₂ figure. It also says that, as the product monitors the combustion continuously, you do not need to check the combustion.
Not given in MINot given in MI
CO₂ at low rate
Not given in MINot given in MI
Maximum CO
More infoHide infoBenchmark flowchart (Appendix G), at maximum and minimum rate. The same flowchart’s re-check box (after checking the burner, internal flue, door and case seals) says less than 335 ppm instead. The manual doesn’t explain the difference.
Less than 350 ppmLess than 350 ppm
CO/CO₂ ratio
More infoHide infoBenchmark flowchart (Appendix G), at maximum and minimum rate.
Less than 0.004Less than 0.004
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoSection 7.13.3: at the measuring nipple on the gas valve, boiler at full load in check programme P.01, measured against atmospheric pressure. Nominal gas connection pressure (technical data): NG 20.0 mbar, LPG (G31 propane) 37.0 mbar. Diagnostics code D.087 also has a Propane 50 mbar setting; the manual gives no working pressure range for it.
Gas valve test point
13.0–23.0 mbar
Gas valve test point
23.0–43.0 mbar
Gas rate at maximum
More infoHide infoTechnical data: at 15 °C and 1013 mbar, based on hot water generation. Section 7.13.2: measure at the gas meter, front casing fitted, after at least 5 minutes in check programme P.01. That section also has a natural gas rate table listed by Qnw from the data plate (nominal, +5%, −10%), but the manual doesn’t say which row is the 627.
3.2 m³/h2.35 kg/h
Flue integrity
More infoHide infoBenchmark flowchart (Appendix G): at the air inlet test point, boiler at maximum rate. Section 9.1 (troubleshooting) gives different figures as signs of recirculation at the air test point: O₂ in the intake air < 20 vol.% or intake air CO ≥ 100 ppm. The manual doesn’t explain the difference.
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 0020193966_02 (20.10.2017)

Enter service mode for high and low rate

High rate

Steps not added yet. Follow the MI.

Low rate

Steps not added yet. Follow the MI.
Ending the test: follow the MI.

Models and GC numbers

ModelGC numberGas
ecoTEC exclusive 627 (VU 256/5-7 (H-GB))41-694-02Not stated

Source: ecoTEC exclusive 627 (VU 256/5-7 (H-GB)) installation and maintenance instructions, 0020193966_02 (20.10.2017).

Sections: 2.3 Validity of the instructions; 3.2 Information on the identification plate; 5.1.1 Information on liquefied petroleum gas operation; 7.3.9 Gas type; 7.6 Using check programmes; 7.13.1 Checking the leak-tightness of the flue gas installation and flue gas recirculation; 7.13.2 Checking the gas flow rate; 7.13.3 Checking the gas flow pressure; 7.13.4 Calibrating the heat generator and measuring the CO/CO₂ content and gas flow in heating mode; 7.13.5 Calibrating the heat generator and measuring the CO/CO₂ content and gas flow in cylinder charging mode; 9.1 Comfort protection mode for the heat cell; Appendix B Overview of diagnostics codes (D.087); Appendix G Commissioning checklist (Benchmark CO and combustion ratio check); Appendix J Technical data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.