Worcester Bosch Greenstar 8000 Style combi (GR8700iW 30 C, 35 C, 40 C, 45 C, 50 C and CB)

Combi, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoFrom Tables 22 and 23 (MI 8.7 and 8.10), boiler at maximum in chimney sweep mode. CO₂ should be measured 10 minutes after firing, with the combustion chamber cover on (MI 8.10). The technical data (MI 12.1) gives the same figures without a tolerance, for every size. CB models have a black front panel and share the figures.
9.5% ± 0.410.8% ± 0.4
CO₂ at low rate
More infoHide infoFrom Tables 22 and 23, boiler at minimum in chimney sweep mode, cover on, 10 minutes after firing. The technical data gives the same figures without a tolerance, for every size.
8.6% ± 0.410.2% ± 0.4
Maximum CO
More infoHide infoThe MI gives two limits. Tables 22 and 23 give <250ppm at maximum and <75ppm at minimum, and MI 8.10.1 says the CO content must be < 250 ppm. The commissioning checks flow chart (MI 6.9, Fig. 67) uses CO < 350ppm at both maximum and minimum rate. The MI doesn’t say which takes priority.
Max rate
<250ppm
Min rate
<75ppm
Flow chart
< 350ppm
Max rate
<250ppm
Min rate
<75ppm
Flow chart
< 350ppm
CO/CO₂ ratio
More infoHide infoFrom the commissioning checks flow chart (MI 6.9, Fig. 67), at maximum and minimum rate. MI 6.7 says to refer to the technical data for CO/CO₂ ratios, but the technical data doesn’t give any.
< 0.004< 0.004
O₂ at high rate
More infoHide infoFrom Tables 22 and 23. No tolerance given.
4.0%4.6%
O₂ at low rate
More infoHide infoFrom Tables 22 and 23. No tolerance given. MI 8.10.1 says to set the CO₂ or O₂ content at minimum rated output.
5.5%5.5%
Working inlet pressure
More infoHide infoFrom Table 16 and Figs. 65 and 66 (MI 6.6), boiler at maximum in chimney sweep mode. At the meter: NG 19–23 mbar. At the LPG storage/supply: 32–45 mbar. The MI splits the gas valve figure at 40 kW without saying which models that covers. The MI text says the drop from the meter or LPG supply to the gas valve must be no more than 2.5 mbar (NG ≤ 40 kW), 3.5 mbar (NG > 40 kW) or 4 mbar (LPG), but Table 16 allows up to 5 mbar for LPG > 40 kW. Table 16 gives a 2.5 mbar LPG pipework drop where Fig. 66 shows 2.0 mbar.
Appliance inlet
18–22 mbar
Gas valve test point
16.5–20.5 mbar (≤ 40 kW), 15.5–19.5 mbar (> 40 kW)
Appliance inlet
29.5–42.5 mbar
Gas valve test point
28–41 mbar (≤ 40 kW), 27–40 mbar (> 40 kW)
Gas rate at maximum
More infoHide infoGas flow maximum rate, 10 minutes from lighting (MI 12.1, Tables 26–28), for C and CB models. Measure at the gas meter after at least 10 minutes at maximum in chimney sweep mode, with all other gas appliances off (MI 6.7). Running a hot water tap doesn’t guarantee maximum output. Where there’s no gas meter (e.g. LPG), check CO/CO₂ instead.
30
3.2 m³/h
35
3.6 m³/h
40
4.3 m³/h
45
4.6 m³/h
50
5.1 m³/h
30
2.3 kg/h
35
2.7 kg/h
40
3.2 kg/h
45
3.4 kg/h
50
3.8 kg/h
Flue integrity
More infoHide infoAt the air inlet sample point on the flue turret/adaptor, casing on, boiler at maximum in chimney sweep mode, readings allowed to stabilise (MI 6.10). Readings outside these limits mean a problem with the flue system or combustion circuit.
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 6720883864 (2019/02)

Enter service mode for high and low rate

High rate

  1. Hold ok for 5 seconds. Press ok when the countdown finishes and Chimney sweep shows.
  2. Confirm the query with Yes.
  3. Use ▲ to set maximum rated output. It’s accepted after 2 seconds and marked with a tick.

Low rate

  1. Use ▼ to set minimum rated output. It’s accepted after 2 seconds and marked with a tick.
  2. Use ▲ to go back to maximum.
Ending the test
  • Press ok or ↩ to come out. It also ends by itself after 30 minutes.

Models and GC numbers

ModelGC numberGas
GR8700iW 30 C NG47-800-03NG
GR8700iW 35 C NG47-800-02NG
GR8700iW 40 C NG47-800-01NG
GR8700iW 45 C NG47-406-99NG
GR8700iW 50 C NG47-406-98NG
GR8700iW 30 CB NG47-406-97NG
GR8700iW 35 CB NG47-406-96NG
GR8700iW 40 CB NG47-406-95NG
GR8700iW 45 CB NG47-406-94NG
GR8700iW 50 CB NG47-406-93NG
GR8700iW 30 C LPG47-800-13LPG
GR8700iW 35 C LPG47-800-12LPG
GR8700iW 40 C LPG47-800-11LPG
GR8700iW 45 C LPG47-800-10LPG
GR8700iW 50 C LPG47-800-09LPG
GR8700iW 30 CB LPG47-800-08LPG
GR8700iW 35 CB LPG47-800-07LPG
GR8700iW 40 CB LPG47-800-06LPG
GR8700iW 45 CB LPG47-800-05LPG
GR8700iW 50 CB LPG47-800-04LPG

Source: Greenstar 8000 Style GR8700iW C gas fired condensing combi boiler installation and maintenance instructions, 6720883864 (2019/02).

Sections: 3.5 Appliance type overview; 6.4 Chimney sweep mode; 6.6 Checking gas inlet pressure; 6.7 Checking the gas rate; 6.9 CO and combustion check; 6.10 Checking flue integrity; 6.11 Flue gas analysis; 8.7 Flue gas analysis; 8.10 Setting the air/gas ratio; 12.1 Technical data.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.