Worcester Bosch Greenstar FS CDi ErP Regular (30CDi, 42CDi)

Floor-standing regular boiler, natural gas and LPG

Combustion figures

FigureNatural gas (G20)LPG (G31)
CO₂ at high rate
More infoHide infoMeasured 10 minutes after firing, with the combustion chamber cover on (MI 6.8, Table 13). Table 4 (MI 2.2) gives the same figures without a tolerance.
9.4 ±0.2%10.8 ±0.2%
CO₂ at low rate
More infoHide infoAllow about 10 minutes at minimum to settle, with the combustion chamber cover on (MI 6.6, 6.8). Table 4 (MI 2.2) gives the same figures without a tolerance.
30CDi
8.6 ±0.2%
42CDi
9.0 ±0.2%
10.4 ±0.2%
Maximum CO
More infoHide infoThe manual gives two limits. The commissioning flow chart (MI 5.6, Fig. 38) says CO < 350ppm at maximum and minimum rate. Table 13 and the air/gas ratio steps (MI 6.8) say less than 200 ppm, and the flue gas analysis (MI 6.6) says to check readings against Table 13. Both shown as printed.
Commissioning check
< 350ppm
Air/gas ratio table
less than 200 ppm
Commissioning check
< 350ppm
Air/gas ratio table
less than 200 ppm
CO/CO₂ ratio
More infoHide infoThe manual gives two limits. The commissioning flow chart (MI 5.6, Fig. 38) says CO/CO₂ ratio < 0.004. Table 13 (MI 6.8) gives 0.002. Both shown as printed.
Commissioning check
< 0.004
Air/gas ratio table
0.002
Commissioning check
< 0.004
Air/gas ratio table
0.002
O₂
Not given in MINot given in MI
Working inlet pressure
More infoHide infoAt the meter or regulator: NG 19–23, LPG 32–45 mbar. Measure with the boiler at maximum and all other gas appliances working. The drop from meter to gas valve must not be more than 2.5 mbar (NG) or 4 mbar (LPG).
Appliance inlet
18–22 mbar
Gas valve test point
16.5–20.5 mbar
Appliance inlet
29.5–42.5 mbar
Gas valve test point
28–41 mbar
Gas rate at maximum
More infoHide infoMeasured at the gas meter after 10 minutes at maximum. NG figures assume a CV of 1040 Btu/ft³ (38.76 MJ/m³). At test gas G20 (37.78 MJ/m³): 30CDi 3.27, 42CDi 4.4 m³/h. Where there’s no gas meter (e.g. LPG), check CO/CO₂ instead (MI 5.5.2).
30CDi
3.19 m³/h
42CDi
4.29 m³/h
30CDi
2.3 kg/h
42CDi
3.3 kg/h
Flue integrity
More infoHide infoAt the air inlet sample point, combustion cover on, boiler at maximum.
O₂ ≥ 20.6%
CO₂ < 0.2%
O₂ ≥ 20.6%
CO₂ < 0.2%

From 6 720 818 079 (2016/04)

Enter service mode for high and low rate

High rate

  1. Hold the Service engineer button (chimney sweep symbol) for 10 seconds. It lights up steady and the blue power light pulses five times.
  2. Turn the temperature control to maximum. The boiler goes to maximum.

Low rate

  1. Turn the temperature control to minimum. The boiler goes to minimum.
  2. Turn the temperature control back to maximum to return to maximum.
Ending the test
  • Press the Service engineer button again to come out. MI 6.8 says hold it over 1 second in one place and 2 seconds in another.
  • The blue power light goes back to steady. It also ends by itself after 15 minutes.

Models and GC numbers

ModelGC numberGas
FS 30CDi ErP Regular41-406-62NG
FS 42CDi ErP Regular41-406-64NG
FS 30CDi ErP Regular LPG41-406-63LPG
FS 42CDi ErP Regular LPG41-406-65LPG

Source: Worcester Greenstar FS 30CDi ErP &amp; 42CDi ErP Regular installation, commissioning and servicing instructions, 6 720 818 079 (2016/04).

Sections: Cover (GC numbers); 2.2 Technical data; 5.5 Checking gas inlet pressure; 5.6 CO and combustion check; 6.5 Checking the flue integrity; 6.6 Flue gas analysis; 6.8 Setting the air/gas ratio.

Spotted something wrong? Tell us.

Check these figures against the MI for the appliance in front of you, matched by GC number and manual date. Combustion work needs a calibrated analyser and a Gas Safe registered engineer.